Description
The ZW32G-12 outdoor circuit breaker is a high-performance power distribution equipment with a rated voltage of 12kV and three-phase AC 50Hz. It is mainly used for various current handling operations in power systems, such as cutting off, closing load currents, overload currents, and short-circuit currents. It is widely applied in substations, industrial and mining power distribution systems, and rural power grids, especially suitable for areas with frequent operations. Moreover, with the addition of a controller, it can achieve distribution network automation, greatly enhancing the operation efficiency and intelligent level of the power system.
- Altitude: This circuit breaker can operate stably at altitudes up to 2000 meters, meeting the power demands in different geographical environments.
- Temperature Range: The ambient air temperature adaptation range is from -45°C to +70°C, with a daily temperature difference of up to 30°C. It can withstand relatively extreme temperature changes, ensuring reliable performance under various climatic conditions.
- Wind Speed: It can resist wind speeds of ≤35m/s, possessing good wind resistance and being suitable for the complex meteorological environment outdoors.
- Safe Environment: It is applicable to places without flammable, explosive, chemically corrosive, and severe vibration hazards, guaranteeing the safety and stability of the equipment operation and reducing the failure risks caused by environmental factors.
High Standard Compliance: It strictly adheres to multiple national and industry standards, such as
- GB1984 “AC High Voltage Vacuum Circuit Breaker”
- GB11022 “General Technical Conditions for High Voltage Switchgear”
- GB311.1 “Insulation Coordination for High Voltage Transmission and Transformation Equipment”
- DL/TS93 “Common Ordering Technical Conditions for High Voltage Switchgear”
- DL/T402 “Ordering Technical Conditions for AC High Voltage Vacuum Circuit Breakers”
- GB2706 “Methods of Dynamic and Thermal Stability Tests for Ac High Voltage Apparatus”
- GB3309 “Mechanical Tests on High Voltage Switchgear under Common Conditions”
- DL403 “Ordering Technical Conditions for 10-35kV Indoor High Voltage Vacuum Circuit Breakers”
No. |
Item |
Unit |
Data |
1 |
Rated Voltage |
KV |
12 |
2 |
Rated Frequency |
HZ |
50 |
3 |
Rated Current |
A |
630 |
1250 |
4 |
Rated Short-Circuit Breaking Current |
KA |
20 |
25 |
5 |
Rated Peak Withstand Current (Peak) |
KA |
50 |
63 |
6 |
Rated Short-Time Withstand Current |
KA |
20 |
25 |
7 |
Rated Short-Circuit Closing Current (Peak) |
KA |
50 |
63 |
8 |
Mechanical Life |
Times |
10000 |
9 |
Rated Short-Circuit Breaking Current Breaking Times |
Times |
30 |
10 |
Power Frequency Withstand Voltage (1min): Wet/Dry,
Phase-to-Phase/Phase-to-Ground |
KV |
30/42/48 |
11 |
Lightning Impulse Withstand Voltage (Peak):
Phase-to-Phase/Phase-to-Ground |
KV |
75/85 |
12 |
Secondary Circuit 1min Power Frequency Withstand Voltage |
KV |
2 |

ZW32G-12 Structure and Installation Dimensions

Technical Requirements
1.Unspecified tolerances are manufactured according to GB/T1804-2000-m level.
2.Unspecified chamfers are 0.545°.
ZW32G-12G Structure and Installation Dimensions

ZW32G-12 Structural Diagram and Installation Dimensions

ZW32G-12G Structural Diagram and Installation Dimensions