Description
Modular Operating Mechanisms VCB is suitable for MV switchgear and is characterised by the modular design of the operating mechanism of this type of VCB
Operating Environment:
- Ambient Temperature: Not exceeding +40°C, not less than -15°C (storage at -30°C is not allowed).
 - Altitude: Not exceeding 1000m.
 - Relative Humidity: Daily average not exceeding 95%, monthly average not exceeding 90%. Daily average saturation vapor pressure not exceeding 22×10-3MPa, monthly average not exceeding 18×10-3MPa.
 - Seismic Intensity: Not exceeding level 8.
 - Application Sites: Suitable for use in places without fire, explosions, severe pollution, chemical corrosion, and severe vibration.
 
Key Technical Parameters:
- Rated Insulation Level: 75kV
 - Rated Lightning Impulse Withstand Voltage: 42kV
 - Rated Current: 630A, 1250A, 1600A, 2000A, 2500A, 3150A, 5000A
 - Rated Short-Circuit Breaking Current: 25kA, 31.5kA, 40kA
 - Rated Short-Circuit Making Current (Peak): 63kA, 80kA, 100kA
 - Rated Short-Circuit Duration: 4 seconds
 - Rated Operating Sequence: O-0.3s-CO-180s-CO or O-180s-CO-180s-CO (40kA)
 - Rated Single/Back-to-Back Capacitor Bank Breaking Current: 630A/400A
 - Number of Operations at Rated Short-Circuit Breaking Current: 30 times
 - Closing Time: 30-70ms
 - Opening Time: 20-50ms
 - Mechanical Life: 30,000 operations
 - Rated Energy Storage and Operating Voltage: AC220/110V, DC220/100V
 - Contact Gap: 11±1mm
 - Overtravel of Contact: 3.5±0.5mm
 - Average Closing Speed: 0.5-0.8m/s
 - Average Opening Speed: 0.9-1.2m/s
 - Contact Bounce Time at Closing: ≤2ms
 - Synchronization Time for Three-Phase Opening and Closing: ≤2ms
 - Main Circuit Resistance: ≤50μΩ (630A), ≤45μΩ (1250A), ≤35μΩ (1600-2000A), ≤25μΩ (2500A and above)
 
Product Features:
- Wide Applicability: The Modular Operating Mechanisms VCB VSG-12 indoor high-voltage vacuum circuit breaker is suitable for a variety of environments and is particularly well-suited for applications requiring frequent operations and high reliability in power systems.
 - Modular Design: The operating mechanism uses a modular design, providing the convenience of quick replacements and assembly.
 - Safety and Reliability: It boasts outstanding electrical performance, reliably protecting and controlling power equipment.
 - Long Mechanical Life: With a high mechanical life, it can withstand extended periods of use.
 - Advanced Design: Features like contact gap and contact overtravel ensure high performance and reliability.
 

If you need a quote or more information about this product, please send us a message and we will get back to you within 1 working day.
Please select the method below:
Message Form
Mobile/Whatsapp: +8613396988128
Linkedin
															