Description
The GCS series low-voltage draw-out switchgear is designed for AC 50/60Hz low-voltage distribution systems with a rated voltage range of 380V to 660V. It serves as core equipment for power distribution, conversion and control, and is widely used for both power distribution and motor control scenarios.
Key Structural Features
- The main cabinet frame is made of section steel, with standard 20mm-modulus mounting holes on both sides, enabling highly flexible internal assembly to adapt to various functional units.
- Adopting a draw-out functional unit design, units of the same specification are fully interchangeable, facilitating on-site maintenance and replacement and greatly reducing power outage duration during operation.
- The interior is divided into independent compartments including busbar chamber, functional unit chamber and cable chamber, which improves operational safety and fault isolation performance.
Technical Specifications
Parameter Category Specification Rated working voltage AC 380/400/660V Rated voltage of auxiliary circuit AC 220/380/400V; DC 110/220V Rated frequency 50/60Hz Rated insulation voltage 660V / 1000V Rated current of horizontal busbar ≤4000A Rated current of vertical busbar (MCC) 1000A Short-time withstand current of busbar (0.1s) 50kA / 80kA Peak withstand current of busbar 105kA / 176kA Power frequency withstand voltage (1min) Main circuit: 2500V; Auxiliary circuit: 1760V Wiring system Three-phase four-wire system, three-phase five-wire system Enclosure protection degree IP30, IP40 Operating Environment
For indoor installation only. Normal operating conditions: altitude ≤2000m, ambient temperature -5℃ to +40℃, no severe vibration, and no strong corrosive, flammable or explosive gases in the surrounding air.Application Scenarios
Suitable for low-voltage distribution systems in power plants, industrial and mining enterprises, high-rise buildings and other facilities.