| General specifications | Product Name | Eaton Moeller® series DILM auxiliary contact module | 
|  | Catalog Number | 277377 | 
|  | Model Code | DILM32-XHI22 | 
|  | EAN | 4015082773779 | 
|  | Product Length/Depth | 45 mm | 
|  | Product Height | 38 mm | 
|  | Product Width | 36 mm | 
|  | Product Weight | 0.048 kg | 
|  | Certifications | UL File No.: E29184 CSA CSA-C22.2 No. 14-05 IEC/EN 60947-4-1 IEC/EN 60947 CE UL 508 UL Category Control No.: NKCR CSA File No.: 012528 UL VDE 0660 CSA Class No.: 3211-03 | 
| Product specifications | Rated operational current for specified heat dissipation (In) | 4 A | 
|  | Terminal capacity (flexible with ferrule) | 2 x (0.75 – 2.5) mm² 1 x (0.75 – 2.5) mm² | 
|  | 10.11 Short-circuit rating | Is the panel builder’s responsibility. The specifications for the switchgear must be observed. | 
|  | Ambient operating temperature (enclosed) – min | 25 °C | 
|  | Lamp holder | None | 
|  | 10.4 Clearances and creepage distances | Meets the product standard’s requirements. | 
|  | 10.12 Electromagnetic compatibility |  | 
|  | Mounting method | Front fastening | 
|  | 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. | 
|  | Ambient operating temperature (enclosed) – max | 40 °C | 
|  | 10.2.3.1 Verification of thermal stability of enclosures |  | 
|  | Ambient storage temperature – min |  | 
|  | Fitted with: | Interlocked opposing contacts | 
|  | 10.8 Connections for external conductors | Is the panel builder’s responsibility. | 
|  | Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) | 
|  | Ambient operating temperature – max | 60 °C | 
|  | Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30 Damp heat, constant, to IEC 60068-2-78 | 
|  | Features | Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L) | 
|  | Lifespan, electrical | 1,300,000 Operations (at 230 V, AC-15, 3 A) | 
|  | Static heat dissipation, non-current-dependent Pvs | 0 W | 
|  | Rated operational current (Ie) at AC-15, 500 V | 1.5 A | 
|  | 10.9.3 Impulse withstand voltage |  | 
|  | Number of poles | Four-pole | 
|  | Ambient operating temperature – min | -25 °C | 
|  | 10.6 Incorporation of switching devices and components |  | 
|  | 10.5 Protection against electric shock |  | 
|  | Safe isolation | 400 V AC, Between auxiliary contacts, According to EN 61140 400 V AC, Between coil and auxiliary contacts, According to EN 61140 | 
|  | Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 6 A | 
|  | Electric connection type | Screw connection | 
|  | 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | 
|  | 10.2.6 Mechanical impact |  | 
|  | 10.9.4 Testing of enclosures made of insulating material |  | 
|  | Number of contacts (normally closed contacts) | 2 | 
|  | 10.3 Degree of protection of assemblies |  | 
|  | Heat dissipation per pole, current-dependent Pvid | 0.16 W | 
|  | Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V |  | 
|  | Switching capacity (auxiliary contacts, general use) | 10 A, 600 V AC, (UL/CSA) 1 A, 250 V DC, (UL/CSA) | 
|  | Number of switches (fault signal) | 0 | 
|  | Equipment heat dissipation, current-dependent Pvid |  | 
|  | Heat dissipation capacity Pdiss |  | 
|  | Rated operational current (Ie) at DC-13, 60 V | 1 A | 
|  | Conventional thermal current ith at 60°C (3-pole, open) | 16 A | 
|  | Rated operational current (Ie) | 1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series) 3 A at 110 V, DC L/R ≤ 15 ms (with 1 contact in series) 6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series) 10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series) | 
|  | Short-circuit protection rating without welding | 10 A gG/gL, 500 V, Max. Fuse, Contacts | 
|  | Terminal capacity (solid) | 1 x (0.75 – 2.5) mm² 2 x (0.75 – 2.5) mm² | 
|  | 10.2.3.2 Verification of resistance of insulating materials to normal heat |  | 
|  | 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |  | 
|  | Connection type |  | 
|  | Rated operational current (Ie) at DC-13, 220 V, 230 V | 0.25 A | 
|  | Terminal capacity (solid/stranded AWG) | 18 – 14 | 
|  | 10.9.2 Power-frequency electric strength |  | 
|  | Control circuit reliability | < 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA) | 
|  | Overvoltage category | III | 
|  | Degree of protection | IP20 | 
|  | Ambient storage temperature – max | 80 °C | 
|  | Rated operational voltage (Ue) at AC – max | 500 V | 
|  | Pollution degree | 3 | 
|  | 10.7 Internal electrical circuits and connections |  | 
|  | Rated impulse withstand voltage (Uimp) | 6000 V AC | 
|  | 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | 
|  | Functions | For standard applications | 
|  | Tightening torque | 1.2 Nm, Screw terminals | 
|  | Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver 2, Terminal screw, Pozidriv screwdriver | 
|  | Type | Front mounting auxiliary contact | 
|  | 10.2.2 Corrosion resistance |  | 
|  | 10.2.4 Resistance to ultra-violet (UV) radiation |  | 
|  | 10.2.7 Inscriptions |  | 
|  | Number of contacts (normally open contacts) |  | 
|  | Short-circuit protection rating | Max. 10 A gG/gL, Fuse, Without welding, Auxiliary contacts | 
|  | Model | Top mounting | 
|  | Rated operational current (Ie) at DC-13, 110 V | 0.5 A | 
|  | Number of contacts (change-over contacts) |  | 
|  | Shock resistance | 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms | 
|  | Switching capacity (auxiliary contacts, pilot duty) | A600, AC operated (UL/CSA) P300, DC operated (UL/CSA) | 
|  | Rated insulation voltage (Ui) | 690 V | 
|  | Rated operational current (Ie) at DC-13, 24 V | 2.5 A | 
| Catalogs | Product overview for machinery |  | 
|  | Switching and protecting motors – catalog |  | 
|  | Product Range Catalog Switching and protecting motors |  | 
|  | SmartWire-DT Catalog |  | 
| Certification reports | DA-DC-00004110.pdf |  | 
|  | DA-DC-00004245.pdf |  | 
|  | DA-DC-00004246.pdf |  | 
|  | DA-DC-00004109.pdf |  | 
| Drawings | 210T013 |  | 
|  | eaton-contactors-frame-dilm-dimensions.eps |  | 
|  | 2110DIM-1 |  | 
|  | eaton-contactors-module-dilm-dimensions.eps |  | 
|  | eaton-contactors-contact-dilm-accessory-3d-drawing-008.eps |  | 
|  | 210I105 |  | 
| eCAD model | ETN.DILM32-XHI22 |  | 
| Installation instructions | IL03407013Z |  | 
| mCAD model | DA-CS-dil_m32_xhi_4 |  | 
|  | DA-CD-dil_m32_xhi_4 |  | 
| Specifications and datasheets | Eaton Specification Sheet – 277377 |  | 
| Wiring diagrams | 210S031 |  | 
|  | 2100SWI-120 |  | 
|  | eaton-contactors-contact-dilm-accessory-wiring-diagram-010.eps |  | 
| Date | Thu Jul 20 2023 |  |